Millbank system is bespoke. 

Please follow below 


To manually check outputs from Extension module to UFH wiring centre:

  • 12V DC should be constant at the Extension module and the Wiring Centre.


  • Turn on DIP SW 1 + 2 

            Outputs 1 - 4 will now be energised 

            Check Voltage out is sufficient for Wiring Centre (2V DC or Higher)


  • Turn on DIP SW 1 + 3 

            Outputs 5 - 8 will now be energised 

            Check Voltage out is sufficient for Wiring Centre (2V DC or Higher)


To check Analogue 10K NTC sensors for UFH only zones

  • Inputs A1 - A8 are used with 10K NTC sensors. 

            A1 = Zone 19, 

            A2 = Zone 20, 

            A3 = Zone 21,

            A4 = Zone 22,

  • If voltage is 0V - 0.5V = Short Circuit - check cable / sensor 
  • If voltage is 3V - 3.5V = Open Circuit - No sensor or broken cable 
  • If voltage is 2V = approx 18 degrees
  • If voltage is 1.9V = approx 20 degrees
  • If voltage is 1.8V = approx 22 degrees
  • If voltage is 1.7V = approx 24 degrees 
  • If voltage is 1.6V = approx 26 degrees
  • If voltage is 1.5V = approx 28 degrees