ORC-HAGW-2 at Millbank has specific code to assist in installation environment.
Web page current state is http://IPADDRESS/ergon/debug/
REG = this value is -1 from zone ( example zone 7 would show in REG 6 )
AMB = Ambient temperature (this is current temperature in room)
SET = desired temperature
FAN = Fan mode (0=OFF, 1=AUTO) - Mitsubishi controls the fan speeds
MOD = Mode (0=OFF, 1=AUTO, 2=FAN only, 3 = COOL, 4 = HEAT )
SC = Schedule
ICO = icon for state (0 – Cooling; 1 – Heating; 2 – Ventilation; 3 - No show)
not used
BL = Blind status
LI = Lighting Status
OP = Operation state
OC = Occupancy
EXT = External sensor (typically bead or limit sensor)
WARNING do not leave web page open on computer, as this will slow down the Gateway. It should be used for viewing only to check status
V1.0 Standard,
V1.2 added check on network connection to keep alive Switch and services,
V1.4 has memory to store last known user settings. This requires EXT V2 firmware on Extension Module.
V1.4.1 added text on webpage (note NO additional code)
Zones
7 = Lounge
8 = Bedroom 1
9 = Bedroom 2
10 = Bedroom 3
11 = Bedroom 4
19 = Hall
20 = Bathroom 1
21 = Bathroom 2
22 = Bathroom 3