PLEASE NOTE below when running communication cables: 


6.6.1 - Segregating circuits


The 15th and 16th editions of the IEE Wiring Regulations applied segregation of circuits which need to be kept apart by classifying them in four separate categories (the Regs themselves only mentioned three categories, but since two types of circuit both categorised as 3 had to be separated from each other, there were effectively four categories).

The second amendments to BS 7671 (published in 1997) have simplified the situation. There are now only two categories, which are known as voltage bands.


Voltage Band I is defined as levels of voltage which are too low to provide serious electric shocks; effectively this limits the band to extra-low voltage (ELV), including telecommunications, signalling, bell, control and alarm circuits.


Voltage Band II covers all voltages used in electrical installations not included in Band I. This means that all 230/400 V (240/415 V) supplies are included in Band II.


As expected, BS 7671 prohibits Band I and Band II cables sharing the same cable enclosure or multicore cable unless: every cable is insulated for the highest voltage present, or each conductor in a multicore cable is insulated for the highest voltage present, unless conductors of the two bands are separated by an earthed metal screen, or they are installed in separate compartments of a trunking or ducting system, or they are installed on a tray with a partition providing separation, or a separate conduit or ducting system is provided for each band.


This does mean that BS 7671 allows circuits such as those for fire alarm Systems, emergency lighting, telephones, data transmission, intruder alarms, sound systems, bell and call systems, etc., may now be run together without segregation. BS 5838: 1988, on the other hand. makes it clear that fire alarm cables must be separated from all others, and IEE Guidance Note 4 requires that escape lighting cables should be mineral insulated or separated from all others by at least 300 mm.  Care must be taken to ensure that circuits are not affected by electrical interference, both electrostatic (due to electric fields) or electro-magnetic (due to electro-magnetic fields). In some ways this makes the circuit designer's task more difficult, because he must now ensure that there will be no interference, whereas before, he simply had to ensure that the required segregation was employed.


In some instances it will be necessary for circuit outlets for both voltage bands to share a common box; switch plate or block. In such a case, the connections of circuits of differing bands must be segregated by a partition, which must be earthed if of metal.


6.6.2 - Electromagnetic compatibility (EMC)


All electrical equipment must be selected and installed so that it will not affect the supply or cause harmful effects to other equipment. One of the harmful effects is electromagnetic interference (EMI). Whenever current flows in a conductor it sets up a magnetic field; a change in the current will result in a corresponding change in the magnetic field, which will result in the induction of electromotive force (voltage) in any conducting system subject to the field. Whilst induced voltages will usually be very small, they may be considerable when rates of change of current are heavy (for example, circuits feeding lift motors) or when there is a lightning strike in the vicinity.


The effects are most pronounced when large metal loops are formed by circuits (perhaps power and data circuits) which are run at a distance from each other but have common earthing and bonding. Power and data cables need to follow common routes to prevent aerial loops which will be subject to induced e.m.f., but with sufficient spacing to prevent interference between them (see{Table 6.4}). The emission standard is BS EN 50081 and the immunity standard BS EN 50082.


The designer needs to consider EMC when planning an installation, and may decide that some of the following measures are appropriate:


providing surge protectors and filters for sensitive equipment, proper separation of power and other cables to limit electro-magnetic interference (EMI), using bonding connections which are as short as possible, screening sensitive equipment and bonding of metal enclosures, and avoiding inductive loops by using the same route for cables of different systems.

Examples of table references 




Table 6.4 Proposed EMI cable separation distances

Power cable voltage Min. separation btw power & signal cables, m
Power cable current

Min separation btw power & signal cables, m 
115V0.255 A0.24
240V0.4515 A0.35
415V0.5850 A0.50